Description
I just drove by to pick up groceries, and noticed the storage unit holding fireworks is rather close to the pumps and the locations where they refill the tanks.
I just drove by to pick up groceries, and noticed the storage unit holding fireworks is rather close to the pumps and the locations where they refill the tanks.
7 Commentaires
Gilbert 311 (Membre officiel vérifié)
Office of Digital Government - Derek (Membre officiel vérifié)
Gilbert 311 (Membre officiel vérifié)
Office of Digital Government - Derek (Membre officiel vérifié)
Gilbert 311 (Membre officiel vérifié)
Fire - Tim (Membre officiel vérifié)
Fire - Thomas D. (Membre officiel vérifié)
7/1/2021 No violations found upon complaint inspection. Closed.
Per NFPA 1124 Standards - CFRS Facilities and stores shall be 50 Foot away from fuel dispensing facilities,
The storage container which meets the criteria of a Type 4 magazine is 50 foot away from the fuel dispensing pumps and underground storage tanks. The CFRS storage container is 60 feet away from the CFRS Tent. ( Per NFPA 1124 section 7.3.12 requires storage containers to be 10 foot away from tents)
The CFRS Tent is 75 feet away from the fuel dispensing pumps.
No Violations found. Closed.